Troubleshooting Sabroe Compressors – SMC & TSMC Series, MK4 Models

کمپرسور سابرو

Permitted Applications for Sabroe Compressors

Using a Sabroe compressor outside its intended design may result in operator injuries and technical damage to the system. The compressor must only be used for the following purposes. In addition, before carrying out any service work, please read the Ammonia First Aid guidelines.

  • As a refrigeration compressor, operated only within the permissible RPM limits specified in Sabroe Refrigeration references.
  • SMC 100 and TSMC 100 compressors with code S and L are designed exclusively for use with refrigerants R717, R22, R134a, R407C, R404A, and R507.
  • SMC 100 and TSMC 100 compressors with code E are designed exclusively for use with refrigerant R717 (Ammonia).
  • SMC 100 and TSMC 100 compressors with codes S, L, and E must only operate at a maximum design discharge pressure of 25 bar (375 psi).
  • The compressor must not be used for evacuating air or moisture from a refrigeration system.
  • The compressor must not be used for pressure testing of a refrigeration system.
  • The compressor must not be used as an air compressor.

Service and Maintenance of Sabroe Compressor Units

Daily Service of Sabroe Compressors

Daily service mainly consists of visual inspection. Once you are familiar with the normal sounds and vibrations of the unit, compare its daily performance with previous observations. Match the operating data and compressor performance diagrams for consistency.

  • Inspect the compressor unit and ensure noise and vibration levels are within normal limits.
  • Record all operating values in a logbook. Compare daily readings with the previous day to identify any trends. If necessary, create a report for closer analysis.
  • Check the oil level in the oil separator (for screw compressors).
  • Check the oil level in the compressor (for reciprocating compressors).
  • Measure and record the oil pressure.
  • Check the refrigerant charge.
  • Inspect for leaks and eliminate them if found. Leaks may involve oil, refrigerant, cooling water, or brine circuits.

Warning

Daily operation and routine maintenance are normally performed by operators. Any additional servicing that requires system analysis and refrigeration engineering must only be carried out by authorized personnel.

Periodic Service of Sabroe Compressors

Lubrication of the motor and other routine maintenance tasks are typically scheduled based on operating hours, although they may be required earlier if necessary.

Overhaul and Major Service of Sabroe Compressors

For major overhauls and complete rebuilds of Sabroe compressors, the standard procedure is to contact the compressor supplier.

Use of the Sabroe Compressor Troubleshooting Table

In the table below, each possible fault is listed with a brief fault description in the “Fault Description” column, the code for the possible cause in the “Cause Code” column, and the fault code in the “Fault Code” column.

Cause Code Fault Description Fault Code
1-2-3-4-5-6-7-9-10-12-14 Compressor does not start 1
9-10-11-13-21-22-23-24-34-35-36-37-40-41-43-44-51-52-54-56-59 Compressor cycles on and off at short intervals 2
3-5-6-9-10-11-12-13-14-15-17-18-41-42-49-50-55-61 Compressor starts but stops immediately 3
8-21-22-24-41-46-52-53-56-60 Compressor runs continuously 4
16-17-18-19-26-48-49-50-51-52-53-54-56-57-58 Abnormal noise from compressor 5
13-15-17-18-20-21-22-23-24-32-34-35-36-37-40-41-44-45-46-49-50-51-52-23-56-60 Insufficient compressor capacity 6
16-18-26-37-38-39-44-56-61 Compressor knocking during start-up 7
21-23-26-37-39 Compressor knocking during operation 8
25-28-29-30-31-33 High condenser pressure 9
22-32-51-52-54-60 Very low condenser pressure 10
13-17-26-34-39-52-53-54-5-60 High suction pressure 11
11-13-20-21-22-23-32-35-36-37-40-41-42-44-45-56-59 Very low suction pressure 12
12-15-17-18-26-49-50-55 Very low oil pressure 13
11-21-22-23-28-29-30-31-33-34-35-36-37-40-41-46-52-54 High discharge pipe temperature 14
26-32-39 Very low discharge pipe temperature 15
33-34-35-36-37-40-50-52 High oil temperature 16
16-18-20-26-51-57-58 Reduced oil level in crankcase 17
16-26-39-61 Severe foaming of oil in crankcase  18
16-18-26-37-39 Sweating or icing of crankcase 19
13-15-16-17-18-49-55-56 Intermittent capacity control 20

Cause Codes Table

Cause Code Cause Code
Condenser cooling or airflow is excessive 32 Power is off – main switch is off 1
Water valve is closed 33 Fuses blown – connections or wiring are loose 2
External pressure equalizer on expansion valve is closed 34 Voltage is very low 3
Expansion valve blocked by ice, dirt, or wax 35 Control current is off 4
Expansion valve bulb charge is empty 36 Motor protection system is active 5
Expansion valve sensor not properly positioned 37 Check for open circuit 6
Expansion valve is leaking 38 Pump or fan is off 7
Expansion valve provides low superheat 39 Contactor is defective 8
Expansion valve produces high superheat 40 High-pressure control has tripped 9
Liquid or suction line filters are blocked 41 Low-pressure control has tripped 10
Liquid or suction solenoid valve is closed 42 Suction pressure control differential is too small 11
Solenoid valve is leaking 43 Oil pressure control has tripped 12
Evaporator frozen or blocked 44 Capacity control is incorrectly set 13
Cooling air is recirculated 45 Defrost timer has cut off current 14
Refrigeration load on system is excessive 46 Oil charge is low 15
Refrigerant is cold-stored in condenser 47 Compressor capacity very high at start-up 16
Coupling is not aligned or missing bolts 48 Oil pressure very low (pressure control setting) 17
Oil pump defective 49 Oil foaming in crankcase 18
Bearings worn or defective 50 Oil charge too high 19
Piston rings or cylinder defective 51 Poor oil return – oil in evaporators 20
Discharge valve leaking or defective 52 Refrigerant supply is restricted 21
Suction valve leaking or defective 53 Insufficient refrigerant charge 22
Compressor bypass open or safety valve leaking 54 Refrigerant vapor in liquid line 23
Compressor oil filter blocked 55 System leakage present 24
Capacity control defective 56 Refrigerant overcharge 25
Oil return solenoid valve blocked or defective 57 Liquid in suction line 26
Oil return filter blocked 58 Increased evaporator charge at low temperature 27
Compressor capacity too high 59 Condenser cooling or airflow insufficient 28
Compressor capacity too low 60 Condenser or air temperature too high 29
Oil heater element in crankcase defective 61 Non-condensable gases in condenser 30
Condenser needs cleaning 31

This document has been compiled and extracted by Atlas Refrigeration Co. from Sabroe compressor technical references. As the most experienced and reputable company in supplying spare parts and overhauling Sabroe compressors, the company is ready to provide its services.

The S and L models are compatible with multiple refrigerants (R717, R22, R134a, R404A, and R507), while the E model is designed exclusively for ammonia (R717).

Bitzer compressors are produced in two types, semi-hermetic and open type, in which freon gases such as R-22, R-134a, R-404a, etc. can be used in the semi-hermetic models. In open-type models, in addition to Freon refrigerants, it is also possible to use R-717 ammonia refrigerant.

The most frequent issues are “failure to start” and “shutting down immediately after startup,” which are usually related to electrical problems, blown fuses, or protective sensors.

Because it is designed exclusively for refrigerants. Using it outside this scope can cause serious technical damage and pose safety risks for operators.

These are critical warnings. First, check oil levels, the operation of the oil pump, and the condition of the oil filter. If the problem persists, a certified technician should inspect the unit and replace worn components.

Related posts

Sabroe Compressor